Oil tank rules in Northern Ireland

What the building regulations say about a home heating oil tank: bunding, distances from buildings and boundaries, and the base it stands on. Summarised from the Department of Finance's Technical Booklet L.

When a tank must be bunded

A bund is a second skin that holds the oil if the tank leaks. Under the building regulations an above ground tank serving a home must have one (an integrally bunded tank whose bund holds at least 110% of the tank) if any of these apply (Building Regulations (NI) 2012, regulations 69 and 76; Technical Booklet L, section 6):

  • it holds more than 2,500 litres (and less than 3,500 litres)
  • it is within 10 metres of a river, stream, lough or the sea
  • it is within 50 metres of a well, borehole or spring used for drinking water
  • spilt oil could run across hard ground into that water
  • spilt oil could run into an open drain or a loose manhole cover
  • the vent pipe cannot be seen from where the tank is filled

A home storing more than 3,500 litres falls under the Control of Pollution (Oil Storage) Regulations (Northern Ireland) 2010 instead, which require secondary containment.

Distances and fire protection

Fire protection for oil tanks (Technical Booklet L, table 6.1)
Where the tank isWhat is needed
1,800 mm or more from a buildingNo fire protection needed
Less than 1,800 mm from any part of a buildingEaves within 1,800 mm need 30 minutes' fire resistance, extending 300 mm past each side of the tank, and either the nearby wall is solid with 30 minutes' fire resistance, or a fire wall stands between the tank and the building, at least 300 mm higher and wider than the tank
750 mm or more from a boundaryNo fire protection needed
Less than 750 mm from a boundaryA fire wall or fire resistant boundary wall with 30 minutes' resistance, at least 300 mm higher than the tank and 300 mm beyond its ends
Near a boiler flueThe end of any flue should be at least 1,800 mm from the tank, unless a fire wall is between them

The base

The tank should stand on a hard surface of concrete or paving slabs at least 42 mm thick, extending at least 300 mm beyond the tank (or its outer skin if bunded) on every side. Fuel pipework into the house should resist fire and have a fire valve where it enters the building.

Building control

These rules apply to a tank and its pipework outside the house that serves a fixed boiler or stove, once the tank holds more than 90 litres. If you are unsure whether your work needs an application, ask your council's building control: find your council.

This is a plain summary for householders, not the full text. An OFTEC registered installer works to the full booklet and BS 5410, and the booklet itself is the authority.